Modbus
The Modbus module enables reading from and writing to slave Modbus modules.
The module acts as a master and provides access to Modbus slaves using the TCP and RTU protocol variants for both read and write access. For the data read or written, the module provides automatic conversion functions for various data types.
Multiple servers to be read as well as multiple slaves can be configured, which are polled at a configurable interval with various options (Subscription/Poll Group).
The following Modbus read functions are supported:
Read Coils (Function Code 01)
Read Inputs (Function Code 02)
Read Holding Registers (Function Code 03)
Read Input Registers (Function Code 04)
The following Modbus write function is supported:
Write Holding-Registers (Function Code 06)
Two transmission protocols are available:
TCP
RTU
Configuration Parameters
Server
The server configuration for the Modbus module can be adapted to match an existing system or the default configuration can be retained. The following two tables show all configuration parameters for the TCP and RTU connection.
| Parameter | Description |
|---|---|
Server Name | Describes the name of the Modbus master to be read. The name can be freely configured using letters and numbers without special characters. |
Protocol Variant | Selection of the TCP protocol |
IP Adress | Enter the IP address of the Modbus TCP master in the format xxx.xxx.xxx.xxx |
Server Port | The default Modbus TCP port is "502". The port can be adjusted according to the server configuration. |
| Parameter | Description |
|---|---|
Server Name | Describes the name of the Modbus master to be read. The name can be freely configured using letters and numbers without special characters. |
Protocol Variant | Selection of the RTU protocol |
Port Name | Name of the data source in the format /*/* |
Baudrate | Serial interface: data rate (specified by Modbus slave) |
Data Bits | Serial interface: number of data bits (specified by Modbus slave) |
Stop Bits | Serial interface: number of stop bits (specified by Modbus slave) |
Parity | Serial interface: parity setting (specified by Modbus slave) |
Slaves
Within the connection variants of the servers it is possible to access multiple slaves. This is particularly useful for Modbus RTU servers, where multiple slaves with the same connection parameters can be addressed. The distinction between different slaves is made via the Slave ID. It should therefore be unique within a group for each slave. Each Slave ID group can contain its own Poll, Subscription or Setup Groups.
| Parameter | Description |
|---|---|
Slave Name | Name of the Modbus slave |
Slave ID | The ID (0 - 255) of the Modbus slave to be read. |
Setup Groups
Using the Setup configuration, Modbus registers can be written. The setup configuration can be performed for both Modbus TCP and Modbus RTU. On startup or when the configuration changes, the specified values are written to the data registers once. Until all values have been written, all other groups within a slave are paused. The process is executed only once.
| Parameter | Description |
|---|---|
Setup Name | Name of the setup |
Parameter Name | The name can be freely configured using letters and numbers without special characters. |
Write Address | Address of the Modbus register to be written |
Type | Standard data types (UInt16, UInt32, UInt64, Int16, Int32, Int64) are preconfigured. Selection is made via a dropdown menu. |
Value | Value to be written. |
Little Endian | Memory structure toggle (if checked = true, Little Endian is used; otherwise Big Endian) |
Poll Groups
Each Poll Group generates a message (payload type Model). The model corresponds to a message containing values from multiple data points.
| Parameter | Description |
|---|---|
Poll Group Name | Name of the poll group, freely configurable using letters and numbers without special characters. This name corresponds to the name of the area to be read. The name is provided under Scope in evaluations. |
Source | The following source modes are available:
The selected mode specifies which name is written to the SourceHeader. With "UseBoth", the combination ServerName.SlaveName is used in the SourceHeader. |
Interval (ms) | Interval in milliseconds specifying the cycle at which values are polled. |
Output Topic | Name of the output topic. The name can be freely configured using letters and numbers without special characters. |
Field Name | Label of the value to be read. The name can be freely configured using letters and numbers without special characters. |
Function Code | The following function codes are available:
|
Start Register | Register address |
Type | Standard data types are preconfigured. Selection is made via a dropdown menu. |
Length | Number of 16-bit registers to be read |
Endian Mode | Memory structure toggle. The following options are available: * bigEndian * littleEndian * bigEndianByteSwapped * littleEndianByteSwapped |
Value Adjust Gain/Offset | Value post-processing: constant scaling by factor and summand (offset) |
Test | Retrieve the current value. |
The register length and the data type must be consistent. For standard data types, the length is determined automatically based on the preconfiguration. Only the Raw Hex data type is configurable.
Subscription Groups
With the Subscription Group, the slave node is polled at a configured Publishing Interval. Depending on the configuration, data packets are only generated if there has been a change in the timestamp.
This is not a subscription in the sense of the OPC UA specification. Instead, the slave is continuously polled with the resulting load on the slave, master, and network side!
| Parameter | Description |
|---|---|
Subscription Group Name | The name can be freely configured using letters and numbers without special characters. The name is provided under Scope in evaluations. Clicking "Create" creates a new group. |
Source | The following source modes are available:
The selected mode specifies which name is written to the Source Header. With "UseBoth", the combination ServerName.SlaveName is used in the Source Header. |
Publishing Interval (ms) | Interval in milliseconds specifying the cycle at which values are polled. |
Republishing Interval (ms) | Interval in milliseconds specifying the cycle at which the last read values are sent again. |
On Change: | Active: If the Modbus server reports a change, the changed data point is transmitted together with the last read values of the other data points as a model message. |
On Republish: | Active: During republishing, the data points are sent as a single data model message. |
Output Topic | Name of the output topic. The name can be freely configured using letters and numbers without special characters. |
Field Name | Label of the value to be read. |
Function Code | The following function codes are available:
|
Start Register | Register address |
Type | Standard data types are preconfigured. Selection is made via a dropdown menu. |
Length | Number of 16-bit registers to be read |
Endian Mode | Memory structure toggle. The following options are available: * bigEndian * littleEndian * bigEndianByteSwapped * littleEndianByteSwapped |
Value Adjust Gain/Offset | Value post-processing: constant scaling by factor and summand (offset) |
Test | Retrieve the current value. |
Configuration in the UI
After selecting the Modbus module on the start page or via the left menu bar of the RoboGate Edge UI, you will be taken to the Modbus module configuration. The following descriptions are based on the example of a Modbus TCP server.
Configuring a Server
By clicking New in the left menu bar, a new Modbus server can be created and configured (Figure 1).
In the first step, the Server Info and Connection must be configured for the new Modbus server. This also includes creating Modbus slaves.

Once this configuration is saved , the Module State section at the bottom of the page shows whether the module was able to establish a connection to the Modbus server.
One or more Setup, Poll or Subscription Groups can then be created separately for each slave.
Configuring a Group
After entering a name for the corresponding group, a new group is created by clicking "Create". The groups can then be configured with their configuration parameters. The following figures show example configurations for a Setup, Poll and Subscription Group for the created Modbus TCP server and slave.
To check whether a data block has been configured correctly, it can be tested using the arrow in the "Test" column. The read result is displayed after clicking the arrow or updated when changes are made. Initially, no values are displayed.



Once the Modbus server configuration is complete, it can be saved using the "Save Configuration" button in the horizontal menu bar at the top right of the module ([img-modbus-saveConfig]). Saving the complete Modbus module configuration makes it available in RoboGate Edge.
Deleting a Data Field
Within the Modbus server configuration, data fields in the group configurations can be deleted. The data field to be deleted is removed using the delete button . The new Modbus server configuration must then be confirmed using the "Save Configuration" button
. The updated configuration is now available in RoboGate Edge.
Deleting a Group
Within the Modbus server configuration, entire groups can be deleted from the configuration. The group to be deleted is removed using the "Remove" button (Figure 5). The new Modbus server configuration must then be confirmed using the "Save Configuration" button . The updated configuration is now available in RoboGate Edge.

Deleting a Server
Within the Modbus server configuration, a Modbus server can be deleted. Clicking the "Remove" button in the server configuration section deletes the selected server (Figure 6). Saving the Modbus configuration afterwards confirms the deletion.

Resetting the Configuration
The "Reset" button in the horizontal menu bar can be used to easily reset the complete module configuration to factory settings.
After clicking the button, a confirmation dialog with "Yes" and "No" appears, asking whether the operation should actually be performed.
This also deletes the entire history on the RoboGate Edge!